Article 61 - Authorize Disposition of Water-Sewer Storage Building
Saved text from 4 source pages. Transcription and OCR may contain errors; verify figures and wording against the original. Retrieved 2026-10-15.
Source page 1
k ~'~J
9 J
t
L
V
~~
18 02
2 152 0
st 2 33
2432
1 11809~c$
26
J
i
~ 22
zaao ool
~ `
29
ti2oo
!"~\_
`~j
60
z.s <
17500
~
`
~ as.o y~ yN \
' 70498
~/~' d.
z4 ~~ ~
i ts 2 D
,~ss2
of s~
~ 90 ~
H 5.1 ACf
1 17
~ ~ t.b8
21
2.88 AC -
93
~~ 1.5 ACt
g~
~ y, --yam' ~~
41-42
33.53 AC
92_
9 2 ~ ,' _~.
p~ \29 ~ 15.0 ACt
~
9C
~--u-z,_
.~~
° ~~
d ~
~\~ ~s
58-5 ~O~
7 [
~OyJN CANTON
to 0 13 gp~
11 ~p
~ 1O ~o
5000 5700
y~, d
/,~
2 'tO~ 636
~ o ti `~,{n,~/~
8,94 ~ `~' 15 4' ~r~112
34050 '§ 64'x' 1 0
3
~~ ~ ?.0250
~ ~ 76620 4
6830 UE p0 _n
0 ~
~ ~ 58-4 ~ ~'
N418
1 Q0 0 700
PREPARED UNDER THE DIRECTION OF _7
~
THE CAMON BOARD OF ASSESSORS BY
STANTEC, INC.
1 41 POR11AtJD SiRF~'
BOSTON, lM
JULY 1996Source page 2
WATER-SEWER STORAGE BUILDING REVIEW
FEBRUARY 26, 2018
NOTES/RECOMMENDATIONS FROM GRLA REPORT AND COMMITTEE VISIT
A. Structural
a. General
- Second floor joists have lost support
- All walls should be inspected for structural integrity
- Northwest gable wall leaning
- Chimney pulling away
- Second floor stair does not meet code and intermediate landing is in dangerous condition
b. Recommendations
- Second floor should be examined for structural integrity
- Extensive structural repairs are needed for safe occupancy
B. Architectural
a. General
- Groundwater is daylighted in several area with the potential for groundwater contamination
- All brick walls need repointing
- Concrete floors are cracked and entire floor requires repair
- Bridge to water dome is non-structural and poses a danger
- Parking and circulation is insufficient
- The building is not accessible and if renovated must be MAAB complaint
- Mechanical, electrical and plumbing systems are limited
- There is no toilet room
- Double doors on west side are boarded up
- No second safe means of egress
- Northwest gable wall is pulling away from roof structure (4" gap) requiring anchor to roof
- Brick has failed behind the chimney affecting bearing of roof joists
- Brick requires removal &reconstruction
- West gabled dormer is above the structurally deficient wall
- There are no gutter or downspouts
- The condition of the domed circular exterior wall is severely deteriorated
- "Building is in a severe state of disrepair."
- If reutilized building must be 100% renovated with code compliant upgrades to egress,
i nterior finishes, Mechanical systems, electrical systems, plumbing systems, fire protection
systems, parking, access by the disabled.
- Building does retain historical charm
- Stairs to west egress doors are no code compliant
b. Recommendations
- Repoint all brick exterior and interior
- Replace concrete floor
- Further investigate dome bridge for structural integrity
- Provide lift or elevator to ground and second floors
- Remove and replace existing electrical and plumbing systems
- Provide toilets
- Provide second means of egress form building
- Investigate and restructure northwest wall that is 4" out
- Install gutters and downspouts
- Repair dome circular exterior walls
- Investigate condition of fiberglass dome, repair as necessary or abandon Dome
- Provide fire alarm and suppression systemsSource page 3
- Replace non-compliant stairs
- Provide additional parking and circulation
C. ENVELOPE
a. General
- Windows are either non-existent or are sheeted over with plastic
- The Dome brick walls require restacking and repointing
- Dome roof should be inspected for integrity
- Full window replacements are required
- Roof leaking (stains)
b. Recommendations
- Investigate source of leaks and repair
- Replace all windows
- 100% repoint &rebuild failed masonry
- Investigate condition of copper valleys etc. and repair as needed
D. ELECTRICAL
a. General
- Complete changeover of electrical system needed
- There is no life safety emergency lighting in building
- Battery powered exit lighting is not present
- Fire alarm no present
b. Recommendations
- Replace electrical service panel
- Replace all receptacles
- Provide fire alarm system
- Install new lighting
- Replace all manual lighting controls with automatic lighting controls
- Provide life safety emergency lighting
- Provide exit signage
E. HEATING, VENTILATION, AIR CONDITIONING (HVAC)
a. General
- There is limited ductwork to distribute air within the space
- There are no exhaust fans in the building
- The furnace is 20 years old
- There is a 275 gallon oil tank (in same building open to groundwater).
- There are no mechanical ventilation systems in the building
b. Recommendations
The building (should be) is condemned and needs) a full renovation
- Install a new high efficiency gas fired heating system
- Install a new exhaust system
- Remove the old tank and install gas service
- Install new ventilation system
E. PLUMBING
a. General
-Industrial Sink is beyond its useful life
- The sink discharges to the ground (Haz Mat investigation?)
- There is no toilet room
- No fire protection system
b. RecommendationsSource page 4
- New plumbing system with toilet rooms) needed - Sewer connection needed, provide toilets - Install fire protection system (sprinklers) - Install on demand electric hot water heater