The next meeting of the Gridley/Water Sewer Storage Building Task Force is scheduled fior March
12t" at 6 PM in the Paul Carroll room. Here are some of the criteria we talked about using to help
make our recommendation:
Town need for building
- Historical value of building
- Potential town uses
- Potential community uses
- Condition of building
- Costs to repair
- Status of other town &school buildings (priority)
- Zoning, allowed uses
- Town financial condition
- Time
"ttached are two summaries of the building reports on both structures. See you on the 12`n
Charles J. Aspinwall
Town Administrator
801 Washington St.
Canton, MA 02021
781-821-5000 Office
iSource page 2
GRIDLEY SCHOOL BUILDING REVIEW
FEBRUARY 26, 2018
NOTES/RECOMMENDATIONS FROM GRLA REPORT AND COMMITTEE VISIT
A. Structural
a. General
- Foundation walls mortar joints are in poor condition.
b. Recommendations
- Repoint foundation
B. Architectural
a. General
- Walls throughout need repair and repointing
- Stairs have old carpet that should be replaced. Railing is not ADA.
- Flooring and ceiling finishes throughout needs replacement as well as selective door
thresholds.
- Exterior and interior doors need replacement.
- Ceiling tiles in many places are stained and should be replaced.
- The under stair storage area is illegal and contains exposed insulation and electrical conduit.
- The second floor should be inspected for structural integrity.
- Lead paint is certain throughout. Second floor tin ceiling mat be salvageable.
- Upstairs toilet rooms are abandoned and used for storage.
- Doorknobs are not handicapped accessible.
- HP ramp rail needs repainting.
- First floor windows need replacement
- Rear corner gutter is not connected & is causing water damage and rot.
- Front trim boards have water damage.
- Pavement condition is fair to poor throughout the site.
- Only one non-conforming MAAB parking spot
- North entry door leading to ramp is not code compliant.
- Door at midwidth intermediate landing opens back onto landing not code compliant
- Stairway finishes are old, worn and need renovation.
- Hurricane ties should be installed between rafter ends and top plate of outside wall.
- Some hazardous materials (lights, ballast, bulbs)found onsite
b. Recommendations
- Implement a program of pavement repair and improved pavement markings
- Implement a program to bring the accessible parking space, signage, and access aisle into
compliance with MAAB regs.
- AI floor, wall, and ceiling finishes are in poor condition and need replacement
- Handrail and stair work is needed as they are not code compliant.
- North egress door latch proximity to adjacent wall must be addressed.
- A full building renovation is required for continued building service.
- An elevator must be installed to second floor
- There is peeling led paint throughout the building.
- After building is sprinklered and structure is addressed, occupancy of the second floor will be
limited to 49 persons.
- The stair to the second floor stairs must have rails and treads &
Repair peeling paint on the facade must be replaced.
- Peeling Paint on wood trim must be addressed.
- Railing on HP ramp must be repainted.
- Gutters must be reconnected and rotted wood repaired.
- Replace fire alarm system
- Close soffit gapsSource page 3
C. ENVELOPE
a. General
- Roof shingles are at the end of their design life
- Gutter is pulled away from roof.
- Upper windows are boarded up.
- Roof soffit repairs needed
b. Recommendations
- Windows on 1S floor must be replaced.
- Roof shingles must be replaced. Gutters must be reconnected &replaces where needed.
- Rear boarded up widows should be replaced.
- Exterior doors &hardware should be replaced.
- Soffits require repair.
D. ELECTRICAL
a. General
- Panel is in fair to poor condition.
- Fire alarm system is old but in fair condition
b. Recommendations
- Replace electrical service
- Upgrade existing lighting
- Replace fire alarm system
- Replace lighting and controls
- Replace emergency lighting throughout.
- Replace all wiring &receptacles.
- Provide new exterior lighting
E. HEATING, VENTILATION, AIR CONDITIONING (HVAC)
a. General
- Gas forced air furnace is 20 years old.
- Toilet room exhaust fans need replacement
b. Recommendations
Replace furnace, ductwork, registers, grilles, and diffusers
- Install central air.
- Replace exhaust fans.
E. PLUMBING
a. General
- Fixtures are installed low for children and are at the end of their useful life.
- Main Hall sink and cabinet need replacement
- Building has no fire protection system (sprinklers).
- No drinking water fountain is on site
b. Recommendations
- Replace all plumbing fixtures with efficient fixtures
- Upgrade hot water heater
- Replace old sanitary piping with new ABS or PVC piping.
- Install water fountain
-Install sprinkler system
-Replace all sanitary piping